Note: Height of blocks is indicated without taking into account the removable units (candles, deflectors, chimney stack etc.)
Components, dimensions and weight of blocks
| Description |
Lenght, mm |
Width, mm |
Height, mm |
Weight, kg |
| Block of GDS |
12500 |
3000 |
2980 |
17000 |
| Block of valves |
1380 |
3000 |
2980 |
2165 |
| Control-and-measuring equipment |
2000 |
3000 |
2980 |
- |
| Odorizing block BO-300 |
3302 |
1200 |
2300 |
1600 |
| Gas separator |
662 |
573 |
7650 |
154 |
| Gas heater |
6100 |
1832 |
2640 |
7195 |
| Draining container V=2,5 m3 |
2600 |
1220 |
1400 |
1300 |
| Container for odorant V=2 m3 |
6110 |
720 |
1860 |
1050 |
| Main technical characteristics: |
|
| Inlet gas pressure |
1,2...7,5 MPa |
| Quantity of outlets |
2 |
| Outlet gas pressure |
1 outlet 0,3...1,2 MPa; 2 outlet 2...5 kPa |
| Throughput capacity |
1 outlet 50000 m3/h (by Pinlet=3 MPa & Poutlet=0,6 MPa) 2 outlet 400 m3/h |
| Supply voltage |
220/380 V |
| Direct current |
24 V |
Power consumption, no more: - In duty mode - In the moment of automatic system actuation |
480 Wt 600 Wt |
| Temperature of inlet gas |
form 10 to +60 oC |
| Temperature of environment |
from - 40 to +40oC |
| Cleaning system |
gauze filter with cell 40 mk, automatic drop of sediment |
| Heating system |
heater PTPG -30 from 1 to 2 pieces |
| Reduction system |
1 outlet 2 reduction lines RDE-100 and RDU-80-02; 2 outlet PR-04 |
| Odorizing system: automatic odorizing unit with closed |
unit of filling up - BO-300 |
| Automatic control system |
|